SOFTWARE : DIGITAL LOSS AND PARTIAL DISCHARGE ANALYZER 10-100HZ-V2-2.1
THIS
TEST WILL BE PERFORMED BY APPLYING AC VOLTAGE IN STEP OF 20% OF THE RATED PHASE
TO GROUND VOLTAGE TO EACH PHASE SEQUENTIALLY. THE MAX. VOLTAGE WILL BE LIMITED
TO 100% OF THE RATED PHASE TO GROUND VOLTAGE . THE FOLLOWING PARAMETERS WILL BE
MESSURED AND CACULATION.
A.TAN-DELTA
& TAN-DELTA TIP-UP
B.CAPACITANCE
& CAPACITANCE TIP-UP
PROCEDURE:
CONNECTION
R-PHASEàEARTH
Y-B
PHASE SHORT àEARTH
THEN
ANOTHER SAME SEQUENCE FOLLOW
RESULT:
KV
|
PHASE – U |
PHASE – V |
PHASE - W |
PHASE – UVW |
||||
TAN d % |
CAP (pF) |
TAN d % |
CAP (pF) |
TAN d % |
CAP (pF) |
TAN d % |
CAP (pF) |
|
1.20 |
3.23 |
71980 |
3.08 |
72040 |
2.98 |
71850 |
2.35 |
208700 |
2.60 |
3.31 |
72080 |
3.13 |
72110 |
3.12 |
71970 |
2.39 |
208900 |
3.90 |
3.37 |
72070 |
3.21 |
72130 |
3.19 |
71960 |
2.43 |
209000 |
5.10 |
3.40 |
72090 |
3.21 |
72130 |
3.24 |
71990 |
2.51 |
209100 |
6.30 |
3.88 |
72370 |
3.68 |
72420 |
3.69 |
72230 |
2.96 |
209900 |
For what reason to know the TAN DELTA
unequivocally?
What
is the Tan Delta Test?
A
pure insulator when is connected across line and earth behaves as a capacitor.
In an ideal insulator, as the insulating material which acts as dielectric too,
is 100 % pure, the electric current passing through the insulator, only have a
capacitive component. There is no resistive component of the current, flowing
from line to earth through the insulator as in ideal insulating material, there
is zero per cent impurity.
In a
pure capacitor, the capacitive electric current leads the applied voltage by
90o.
In
practice, the insulator cannot be made 100% pure. Also due to the aging of
insulators, the impurities like dirt and moisture enter into them. These
impurities provide the conductive path to the current. Consequently, an
electric leakage current flowing from line to earth through the insulator has a
resistive component.
Purpose
The
main purpose of
the tan delta test is
to make sure of maintaining a secure and reliable functioning of the
transformer. With the calculation of dissipation factor and capacitance
values, it provides the result of insulation behavior
of bushings and in windings too.
Variation
in the capacitance value, for instance, it indicates partial kind of breakdowns
in bushings and automated movement of windings. Insulation deprivation, aging
of the equipment, enhancement in the energy levels is transformed into heat.
The amount of losses in these is calculated as the dissipation factor.
With
the tan delta testing method, one can easily know the dissipation factor and
the capacitance values at the required level of frequencies. So, any kind of
aging factor can be identified earlier and the corresponding action can be
implemented.
Principle of Tan Delta Test
When
a pure insulator has a connection between the earth and the line, then it
performs like a capacitor. In an ideal kind of insulator, as the insulating
substance functions as a dielectric, which is totally pure, then the passage of
current through the material holds only capacitive material. There will be no
resistive element for the electric current that is flowing from the line to the
earth via insulator as in the insulating component, there will be no presence
of impurities. The tan delta test circuit diagram is
shown as follows:
Tan Delta Test Circuit
In a
pure capacitive material, the capacitive current precedes the voltage level by
900. As a general, the insulating material is totally pure, and even because of
the aging properties of the components, the contaminations such as moisture and
dirt might get added. These contaminations create a conductive path for the current.
As a result, leakage current that flows from line to earth via the insulator
holds resistive
elements.
Therefore,
it is pointless to claim that, for a good quality of insulator, this resistive
element of leakage current is correspondingly minimal. In the other aspect, the
behavior of an insulator might be known by the proportion of the resistive
element to that of the capacitive element. For good quality of insulator, this
proportion is correspondingly less and this is termed as tanδ or tan delta. In
a few cases, this is also expressed as a dissipation factor. With the
below-depicted vector diagram, it can be known.
Where
the x-axis represents the level of system voltage which is the resistive
element of leakage current IR. As this capacitive element of leakage current
IC precedes by 900, it is taken across the y-axis.
And
now, the whole leakage current is given by IL(IC + IR)
And from the diagram, tanδ is (IR /IC)
tanδ =
(IR /IC)
Tan Delta Testing Process
The
below process explains the method of tan delta testing in
a step-by-step manner.
The
requirements necessary for this test such as cable, potential transformer,
bushings, current transformer, and winding on which this testing is conducted
has to be initially separated from the system.
The
minimal frequency level of test voltage is applied along with the equipment
where the insulation to be analyzed.
At
first, normal voltage levels are applied. When the tan delta values are as
expected at this voltage level, then the applied voltage level is increased by
2 times as of applied voltage.
The
values of the tan delta are recorded by the tan delta controller.
To
the tan delta calculating component, a loss angle analyzer is connected which
compares tan delta values at higher and general voltage levels and delivers
accurate results.
It
has to be noted that the testing procedure to be carried out at very minimal
frequency levels.
It is
more recommended to conduct testing at minimal frequency levels, because when
the applied voltage level is more, then the capacitive reactance of the
insulator device reaches very minimal, therefore the capacitive element of the
current reaches more. As the resistive element is practically constant; it is
based on the applied voltage level and the insulator’s conductivity value.
Whereas
at increased frequency level the capacitive current, is more, and then the
amplitude of the vector amount of both the capacitive and resistive elements of
the current reaches very high. So, the necessary level of power for the tan
delta test would become more that seems to be not acceptable. Because of this,
the power constraint for dissipation factor analysis, very minimal frequency
test voltage is required.
Predicting
the Test Results
These
exist mainly two approaches to analyze the situation of the insulation method at
the time of tan delta testing. The first is, evaluating the past test results to
know the worsening of insulation conditions because of the aging effect.
Whereas the second scenario is to verify the insulation behavior directly from
tanδ value. Here, there is no necessity of assessing past results with that
tanδ test values.
When
the insulation results are accurate, then the loss factor values are nearly
similar for the entire test voltage values. But, in the case when the
insulation results are not accurate, then the tanδ values get increased for a
higher level of voltages. The increasing tanδ corresponds that, high resistive
current element, happens in insulation. These outcomes might be matched with
the outcomes of past tested insulators, to go with the appropriate decision
either the equipment has to be substituted or not.
This
is the way that how to test the result tan delta testing can be done.
What
are the Different Modes of the Tan Delta Test?
When
it comes to tan delta test, there are essentially three modes of power factor
testing. Those are
GST Guard – This calculates the amount of current
leakage to the ground. This method eliminates the current leakage through red
or blue leads. Whereas in UST, the ground is termed to be guard because
grounded edges are not calculated. When the UST method is applied on the
device, then the current measurement is only through blue or red leads. The
current flow through ground lead gets automatically bypassed to the AC source
and thus excluded from the calculation.
UST Mode – This is employed for the calculation of
insulation in between ungrounded leads of the equipment. Here the individual
portion of isolation has to be separated and analyze it having no other
insulation connected to it.
GST Mode – In this final mode of operation, both
the leakage pathways are calculated by the test apparatus. The current,
capacitance values, UST, and GST guards, loss in watts need to be equal to the
GST test parameters. This provides the entire behavior of the test.
When
the summing value of GST Guard and UST is not equal to the GST parameters, then
it can be known that there is some crashing in the test set, or might the test
terminal are not correctly designed.
On
the whole, this is a detailed explanation of the Tan Delta Test. Here, in this
article, we are completely aware of what is a tan delta test, its principle,
purpose of it, methods, and testing technique. Also know about what are LV to
earth test, HV to earth test, and LV-HV tan delta testing
methodologies?
WHAT IS DISSIPATION FACTOR?
Dissemination
Factor Tan Delta is the proportion of futile flow in the Electrical framework
to a helpful flow in it. That implies this is the proportion of Wattloss
current to the Reactive current in it.
i.e
tan = IR/Ic
For
the voltage applied V
tan =
Watt-misfortune (Active) Power
Thus
tan delta is considered as the proportion of nature of protection in dielectric
material.
In
certain nations Cos is estimated to know the Insulation Quality.
Watt
misfortune in Power System
It is
needed to screen the watt misfortune through the protection of Power System, A
Generator, Transformer, Cable even a Power Capacitor utilized in the Electric
circuit of Generation, Transmission and Distribution will have exceptionally
low influence misfortune.
Eg1 .
The Capacitors, that to be utilized for Power Factor Correction, or a Power
Cable that is utilized in Electric Power Circuit are extremely fundamental to
have exceptionally low wattloss.
for
example 0.2/kVAR for Power Capacitors and tan delta of 0.0005 for Power Cables.
The
Dissipation Factor tan is the immediate proportion of watt misfortune (VAcos)
in the absolute reactance of the Power Capacitor. for example The ostensible
tan delta worth of 0.0002 will be saved for Power Capacitor under use.
To
guarantee the right wattloss/KVAR, the tan delta will be estimated with high
accuracy i.e with the precision 0.00005 or better and this estimating framework
will create repeatable outcomes for a long time.
Eg2
All over the world for a really long time together the information on
Dielectric Material have been recorded and checked. Ordinarily the Insulating
Oil contributes significant part as the dielectric material, in an Electrical
Power Appliance. Subsequently it is exceptionally fundamental to exactly know
the diverse Electrical and Chemical properties of Insulating Oil.
To
know the electrical properties of the Insulating Oil, the tan delta test and to
know the compound debasements the Dissolved Gas Analysis (DGA) of the oil is
led. These two tests are considers similar to the ideal measuring stick for
Failure Analysis and furthermore for Aging Effect of the Power Equipment under
use.
For
crisp protecting Oil the Dissipation Factor is noted utilizing exceptionally
exact instrument. For this situation the Dissipation Factor is just about as
less as 0.0001 and this estimation will be with precision of 0.00005 (0.005%)
of perusing (according to IEC 250).
This
table was genuine tan delta test on generator after fixed from flooded of seal oil.
The test outcome ought to be less that 2 %.
0 Comments