The
value of a test current should be selected according to the nominal winding
current. Information about nominal winding current could be found on the
nameplate of the test object. The test current should not exceed 10% of the
nominal winding current. Because of cables heating, higher values of test
current will significantly increase the winding resistance.
The winding resistance of three-phase AC motors is measured between their terminals (all
three combinations).
Figure
2 – Measuring the stator winding resistance of an AC motor
Figure
3 – Connection for measuring the stator winding resistance of induction motor
Winding
resistance of slip-ring rotor is measured directly on the slip rings
(non-linear transition resistance of brushes is not included in the measured
winding resistance).
Figure
4 – Measuring the winding resistance of the slip-ring rotor
Figure
5 – Results menu of RMO-M
Discharging
Motor After Winding Resistance Test
Be
aware of a possibility the energy still remains in a magnetic circuit. After
the measurement has been completed the RMO-M device will start the current discharging process
automatically. During the current discharging the ”DISCHARGING” message is shown
on the device display.
The
leads should never be removed during the testing process. The operator should
always wait for a discharging signal and a buzzer sound signal to end. That is
an indication the tested motor has been properly discharged.
The
current injection and energy discharging process are fully automatically
regulated. The safe discharging circuit, equipped with an indicator, rapidly
dissipates the stored magnetic energy after the test completion.
CAUTION: The test leads should not be disconnected before the
“Discharging” message disappears from the display and the discharging LED is
off.
After
all the tests have been completed, the test leads are disconnected in the
following order:
the
test leads are removed from the test object
the
test leads are removed from the instrument.
The
mains voltage supply cable is removed first from the supply source, and then
from the instrument. Finally, the ground (PE) cable is removed from the
instrument.
STATOR WINDING RESISTANCE
Temp: 38°C
PHASE |
U |
V |
W |
Resistance in mΩ |
5.304 |
5.312 |
5.295 |
0 Comments