To
assess the mechanical integrity of the Generator end winding, a Natural frequency
test is performed in order to determine the natural frequency response of
individual loops in the radial and axial directions. If the measured natural
frequency values are out of the resonance frequency band 95-100 Hz, it can be
declared that the mechanical integrity of the stator end winding is in
satisfactory condition. If it is out of resonance frequency, end winding has to
be strengthened till the measured frequency values are out of resonance
frequency.