Partial discharges are electrical sparks that
occur in gas voids within the insulation when voltage is high enough. The spark
generates a fast current pulse which travels through the stator winding. The
larger the Pd pulse, the higher the current pulse that reaches the terminals of the
winding. A high voltage capacitor can block the power frequency voltage while
allowing the high-frequency pulse signals to reach a Pd detector. The pulse
signals after further filtering are displayed on an oscilloscope screen. Partial
discharge tests are probably the best means for assessing the insulation
condition without a visual inspection. By measuring the Pd activity of a stator an
indication of the health of the winding can be
obtained. IEEE std for this test: IEEE – Std.
436
Dielectric Discharge (DD) Test is a diagnostic
insulation test that allows aging and deterioration of insulation to be assessed. The
result is dependent on the discharge characteristic so the internal state of
the insulation is tested, largely independent of any surface
contamination. The charge that is stored in the sample is measured during the discharge phase. The
DD test is automatic on some MEGGER® insulation testers making it very simple
to carry out.
Charging Insulation
During an insulation test the charging rate
depends on the capacitance of the sample, the absorption rate, the leakage current
plus the output current of the insulation tester.
Capacitive Charging Current
The insulation material becomes charged in the
same way as a dielectric in a capacitor. This charging is dependent on the
capacitance value and the resistance of the source. This effect usually decays
in a few seconds.
Absorption Current
In addition to the capacitive charging, dipoles
align in the electric field within the material and some charges are able to
move slightly. These charging effects cause absorption current which has a long
time constant. They will return to their natural, random state slowly when the
test voltage has been removed (causing re-absorption current). These effects
are lengthened when the insulation has been contaminated by dirt or moisture.
Depending on the type of insulation this may take as long as 30 minutes.
The leakage current
Leakage Current is dominated by surface leakage but includes
leakage through the insulation. This is the resistive current that would be
measured when the insulation is fully charged and full absorption has taken
place.
Surface leakage can be removed by use of the
'Guard' terminal.
Total Current
The total current is measured by an insulation tester to calculate the insulation resistance. To analyse the insulation,
the time - resistance
characteristics can be used to assess how the charging currents are varying.
The
charging characteristics can be used to assess the quality of the insulation in
the polarization index (10minute:1 minute) or dielectric absorption
(60seconds:30 seconds) tests. These ratios can be used to evaluate the level of
contamination of the sample because the difference between the absorption and
leakage current is measured. Excessive leakage current will swamp absorption
current, leading to a flatter time-resistance curve.
Insulation Discharge
The
charge that is stored during the insulation test is automatically discharged at
the end of the test when the insulation tester's discharge resistors are
switched across the terminals. The rate of the discharge depends only on the discharge resistors and the amount of stored charge from the insulation.
When the voltage across the insulation has reduced to almost zero the effect of
surface leakage will be very small.
The
discharge currents change in a similar way to the charging currents; the
capacitive current decays quickly due to the time constant
of the capacitance and the discharge resistors, the absorption current decays
slowly as re absorption effects take place.
Re absorption Current
The
capacitive current quickly decays from a high value with a relatively short
time constant (a few seconds). The absorption (or re-absorption during a
discharge) current starts from a lower level but has a much longer time constant
(up to several minutes). It is caused by ions and dipoles re-aligning
themselves within the insulation. When an electric field is applied some ions
are able to move and some dipoles align themselves within the field.
These
effects reverse themselves slowly when the test voltage is removed caused by
particles returning to their natural, random state. This can have the effect
of a current flowing if the discharge circuit is still connected, or a voltage reappearing
on the sample if it is left open circuit. The DD test measures
the discharge currents 1 minute after an insulation test has been completed. At
this time the capacitive current has usually become
insignificant compared with the re absorption current. The level of re absorption after
this time shows the state of the insulation material, providing the insulation
has been fully charged for full absorption to take place
(typically 10 to 30 minutes). A high re absorption current shows that the insulation has been
contaminated, usually by moisture. A low
current usually shows that the insulation is clean and has not absorbed
much water.
Dielectric
Discharge Definition
The
dielectric discharge test measures the discharge current 60 seconds after the
insulation test is finished. This is converted to a
figure of merit which gives a figure for the quality of the insulation,
independent of the test voltage. This is temperature
dependent so it is important to test at a reference temperature or record the
value. The DD value is
defined as (in mAV-1F-1):
Multi-layer
Insulation
Insulation
in high voltage equipment often consists of layers, each having its own
capacitance and associated leakage resistance. When insulation is built up
in this way, the aim is to make each layer such that the voltage stress is shared equally
between layers. When the insulator is discharged each layer's charge will
decrease equally until there is no voltage remaining. The DD test result
can also show how similar the layers of insulation are. In the case of
insulation failure in a single layer of insulation the leakage
resistance will decrease but the capacitance is likely to remain the same. This type of fault is not
possible to detect from a standard insulation test because the overall
resistance will remain high due to the other, high resistance, layers.
Similarly, other tests such as time-resistance measurements, step voltage tests or capacitance
measurement will not necessarily show any particular problem. Measuring the
discharge current can show when the resistance-capacitance
characteristic is incorrect. This effect is smaller than the absorption effects
mentioned previously.
DD
Test Result Analysis
A low
DD value shows that the re-absorption current is decaying quickly and the time
constant of each layer of insulation is similar. A high value of DD shows
that the re-absorption current exhibits long relaxation times which may point to a
problem with the insulation. Typical conditions from practical research,
primarily carried out on generators by a major utility, arrived at the
figures of merit in the table below. This technique was developed for HV generators but may
have applications where insulation condition needs to be determined for other
electrical equipment.
CRITERIA
PROCEDURE:
GENERATOR
BUS BAR ßMEGGAR
R-PHASE
APPLY VOLTAGEàEARTH
Y-B
PHASE SHORT AND EARTH
RESULT :
Temp: 38°C
Phase |
DD
Value |
R-Phase |
3.83 |
Y-Phase |
3.32 |
B-Phase |
4.18 |
0 Comments