ECTION1DRY-TYPE DISTRIBUTION TRANSFORMERS
6 ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION • LUMBERTON, NC • 800-334-5214 • www.acmepowerdist.com
1. What is a transformer and how does it work?
A transformer is an electrical apparatus designed to convert
alternating current from one voltage to another. It can be
designed to “step up” or “step down” voltages and works
on the magnetic induction principle. A transformer has no
moving parts and is a completely static solid state device,
which insures, under normal operating conditions, a long and
trouble-free life. It consists, in its simplest form, of two or
more coils of insulated wire wound on a laminated steel core.
When voltage is introduced to one coil, called the primary,
it magnetizes the iron core. A voltage is then induced in the
other coil, called the secondary or output coil. The change of
voltage (or voltage ratio) between the primary and secondary
depends on the turns ratio of the two coils.
2. What are taps and when are they used? Taps
are provided on some transformers on the high voltage
winding to correct for high or low voltage conditions, and still
deliver full rated output voltages at the secondary terminals.
Standard tap arrangements are at two-and-one-half and five
percent of the rated primary voltage for both high and low
voltage conditions. For example, if the transformer has a 480
volt primary and the available line voltage is running at 504
volts, the primary should be connected to the 5% tap above
normal in order that the secondary voltage be maintained at
the proper rating. The standard ASA and NEMA designation
for taps are “ANFC” (above normal full capacity) and “BNFC”
(below normal full capacity).
3. What is the difference between “Insulating,”
“Isolating,”and“Shielded Winding” transformers?
Insulating and isolating transformers are identical. These terms
are used to describe the isolation of the primary and secondary
windings, or insulation between the two. A shielded transformer
is designed with a metallic shield between the primary and
secondary windings to attenuate transient noise. This is
especially important in critical applications such as computers,
process controllers and many other microprocessor controlled
devices. All two, three and four winding transformers are of
the insulating or isolating types. Only autotransformers, whose
primary and secondary are connected to each other electrically,
are not of the insulating or isolating variety.
4. Can transformers be operated at voltages
other than nameplate voltages? In some cases,
transformers can be operated at voltages below the nameplate
rated voltage. In NO case should a transformer be operated at
a voltage in excess of its nameplate rating, unless taps are
provided for this purpose. When operating below the rated
voltage, the KVA capacity is reduced correspondingly. For
example, if a 480 volt primary transformer with a 240 volt
secondary is operated at 240 volts, the secondary voltage is
reduced to 120 volts. If the transformer was originally rated 10
KVA, the reduced rating would be 5 KVA, or in direct proportion
to the applied voltage.
5. Can 60 Hz transformers be operated at 50 Hz?
ACME transformers rated below 1 KVA can be used on 50 Hz
service. Transformers 1 KVA and larger, rated at 60 Hz, should
not be used on 50 Hz service, due to the higher losses and
resultant heat rise. Special designs are required for this service.
However, any 50 Hz transformer will operate on a 60 Hz service.
Transformer Questions & Answers
6. Can transformers be used in parallel? Single
phase transformers can be used in parallel only when their
impedances and voltages are equal. If unequal voltages are
used, a circulating current exists in the closed network between
the two transformers, which will cause excess heating and result
in a shorter life of the transformer. In addition, impedance
values of each transformer must be within 7.5% of each other.
For example: Transformer A has an impedance of 4%, transformer
B which is to be parallel to A must have an impedance
between the limits of 3.7% and 4.3%. When paralleling three
phase transformers,the same precautions must be observed
as listed above, plus the angular displacement and phasing
between the two transformers must be identical.
7. Can Acme Transformers be reverse connected?
ACME dry-type distribution transformers can be reverse
connected without a loss of KVA rating, but there are certain
limitations. Transformers rated 1 KVA and larger single phase,
3 KVA and larger three phase can be reverse connected without
any adverse effects or loss in KVA capacity. The reason for this
limitation in KVA size is, the turns ratio is the same as the voltage
ratio. Example: A transformer with a 480 volt input, 240 volt
output— can have the output connected to a 240 volt source
and thereby become the primary or input to the transformer,
then the original 480 volt primary winding will become the
output or 480 volt secondary. On transformers rated below
1 KVA single phase, there is a turns ratio compensation on the
low voltage winding. This means the low voltage winding has
a greater voltage than the nameplate voltage indicates at no
load. For example, a small single phase transformer having a
nameplate voltage of 480 volts primary and 240 volts secondary,
would actually have a no load voltage of approximately 250 volts,
and a full load voltage of 240 volts. If the 240 volt winding were
connected to a 240 volt source, then the output voltage would
consequently be approximately 460 volts at no load and
approximately 442 volts at full load. As the KVA becomes
smaller, the compensation is greater—resulting in lower output
voltages. When one attempts to use these transformers in
reverse, the transformer will not be harmed; however, the
output voltage will be lower than is indicated by the nameplate.
8. Can a Single Phase Transformer be used on a
Three Phase source? Yes. Any single phase transformer
can be used on a three phase source by connecting the primary
leads to any two wires of a three phase system, regardless
of whether the source is three phase 3-wire or three phase
4-wire. The transformer output will be single phase.
9. Can Transformers develop Three Phase power
from a Single Phase source? No. Phase converters or
phase shifting devices such as reactors and capacitors are
required to convert single phase power to three phase.
10. How do you select transformers?
(1) Determine primary voltage and frequency.
(2) Determine secondary voltage required.
(3) Determine the capacity required in volt-amperes.
This is done by multiplying the load current (amperes) by the
load voltage (volts) for single phase. For example: if the load
is 40 amperes, such as a motor, and the secondary voltage is
240 volts, then 240 x 40 equals 9600 VA. A 10 KVA (10,000
All of these insulation systems will normally have the same
number of years operating life. A well designed transformer,
observing these temperature limits, will have a life expectancy
of 20-25 years.
17. Why should Dry-Type Transformers never
be over-loaded? Overloading of a transformer results in
excessive temperature. This excessive temperature causes
overheating which will result in rapid deterioration of the
insulation and cause complete failure of the transformer coils.
18. Are temperature rise and actual surface
temperature related? No. This can be compared with
an ordinary light bulb. The filament temperature of a light bulb
can exceed 2000 degrees, yet the surface temperature of the
bulb is low enough to permit touching with bare hands.
19. What is meant by “impedance” in
transformers? Impedance is the current limiting characteristic
of a transformer and is expressed in percentage.
20.Why is impedance important? It is used for
determining the interrupting capacity of a circuit breaker or fuse
employed to protect the primary of a transformer. Example:
Determine a minimum circuit breaker trip rating and interrupting
capacity for a 10 KVA single phase transformer with 4%
impedance, to be operated from a 480 volt 60 Hz source.
Calculate as follows:
Normal Full Load Current =
Nameplate Volt Amps = 10,000 VA =
Line Volts 480 V
20.8 Amperes
Maximum Short Circuit Amps =
Full Load Amps 20.8 Amps
4%
=
4%
=
520 Amps
The breaker or fuse would have a minimum interrupting rating
of 520 amps at 480 volts.
SECTION1DRY-TYPE DISTRIBUTION TRANSFORMERS
ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION • LUMBERTON, NC • 800-334-5214 • www.acmepowerdist.com 7
volt-amperes) transformer is required. ALWAYS SELECT THE
TRANSFORMER LARGER THAN THE ACTUAL LOAD. This is
done for safety purposes and allows for expansion, in case more
load is added at a later date. For 3 phase KVA, multiply rated
volts x load amps x 1.73 (square root of 3) then divide by 1000.
(4) Determine whether taps are required. Taps are usually
specified on larger transformers.
(5) Use the selection charts in Section I.
11. What terminations are provided? Primary and
Secondary Terminations are provided on ACME Dry-Type
Transformers as follows:
No lugs—lead type connection on
0-25 KVA single phase
0-15 KVA three phase
Bus-bar terminations
(drilled to NEMA standards)
37.5 -250 KVA single phase
25-500 KVA three phase
12.Can 60 Hz transformers be used at higher
frequencies? ACME transformers can be used at frequencies
above 60 Hz up through 400 Hz with no limitations provided
nameplate voltages are not exceeded. However, 60 Hz transformers
will have less voltage regulation at 400 Hz than 60 Hz.
13. What is meant by regulation in a transformer?
Voltage regulation in transformers is the difference between
the no load voltage and the full load voltage. This is usually
expressed in terms of percentage. For example: A transformer
delivers 100 volts at no load and the voltage drops to 95 volts
at full load, the regulation would be 5%. ACME dry-type
distribution transformers generally have regulation from 2%
to 4%, depending on the size and the application for which
they are used.
14. What is temperature rise in a transformer?
Temperature rise in a transformer is the temperature of
the windings and insulation above the existing ambient or
surrounding temperature.
15. What is “Class” in insulation? Insulation class
was the original method used to distinguish insulating materials
operating at different temperature levels. Letters were used for
different designations. Letter classifications have been replaced
by insulation system temperatures in degrees Celsius. The
system temperature is the maximum temperature at the
hottest spot in the winding (coil). Graphical representations of
six insulation systems recognized by Underwriters’ Laboratories,
Inc. are shown in Figure A. These systems are used by Acme
for a large part of the product line.
16.Is one insulation system better than another?
Not necessarily. It depends on the application and the cost
benefit to be realized. Higher temperature class insulation
systems cost more and larger transformers are more expensive
to build. Therefore, the more expensive insulation systems are
more likely to be found in the larger KVA units.
Referring to Figure A, small fractional KVA transformers use
insulation class 130°C. Compound filled transformers use
insulation class 180°C. Larger ventilated transformers are
designed to use 220°C insulation.
10
Total Winding Temperature °C
COIL HOT SPOT
DIFFERENTIAL
AV. WINDING
RISE
AMBIENT
105
130
180
220
30
25
10
55
80
115
150
AGENCY: UL/ANSI 1561 MARCH 1987
40 40 40 40
Figure A
25. Can transformers listed in this catalog be
reconnected as autotransformers to increase
theirKVArating? Several standard single phase transformers
listed in this catalog can be connected as autotransformers.
The KVA capacity will be greatly increased when used as an
autotransformer, in comparison to the nameplate KVA as an
insulating transformer. Examples of autotransformer applications
are changing 600 volts to 480 volts in either single phase or three
phase; changing 480 volts to 240 volts single or three phase or
vice versa; or the developing of a fourth wire (neutral) from a 480
volt three phase three wire system for obtaining 277 volts single
phase. This voltage is normally used for operating fluorescent
lamps or similar devices requiring 277 volts. For further details
showing KVA and voltage combinations for various autotransformer
connections refer to Page 30 and 31 in this catalog.
26. Are ACME Transformers shown in this
catalog U.L. Listed? All of the transformers, with few
exceptions, are listed by Underwriters’ Laboratories and have
met their rigorous requirements. We are also prepared to have
transformers, which are not presently listed, submitted for
listing to Underwriters’ upon the customer’s request. Please
contact the factory for details.
27. Is CSA certification available for transformers
shown in this catalog? Most ACME transformers shown
in this catalog are certified by Canadian Standards Association.
They have been designed and tested in accordance with the
latest specifications. Please contact the factory if further
details are required.
28.What is BIL and how does it apply to
transformers listed in this catalog? BIL is an
abbreviation for Basic Impulse Level. Impulse tests are dielectric
tests that consist of the application of a high frequency steep
wave front voltage between windings, and between windings
and ground. The Basic Impulse Level of a transformer is a
method of expressing the voltage surge (lightning, switching
surges, etc.) that a transformer will tolerate without breakdown.
All transformers manufactured in this catalog, 600 volts and
below, will withstand the NEMA standard BIL rating, which is
10 KV. This assures the user that he will not experience breakdowns
when his system is properly protected with lightning
arrestors or similar surge protection devices.
29. What is polarity, when associatedwith a
transformer? Polarity is the instantaneous voltage obtained
from the primary winding in relation to the secondary winding.
Transformers 600 volts and below are normally connected in
additive polarity — that is, when tested the terminals of the
high voltage and low voltage windings on the left hand side are
connected together, refer to diagram below. This leaves one
Example: Determine the interrupting capacity, in amperes, of
a circuit breaker or fuse required for a 75 KVA, three phase
transformer, with a primary of 480 volts delta and secondary
of 208Y/120 volts. The transformer impedance (Z) = 5%. If the
secondary is short circuited (faulted), the following capacities
are required:
Normal Full Load Current =
Volt Amps 75,000 VA
√ 3 x Line Volts √ 3 x 480 V
90 Amps
Maximum Short Circuit Line Current =
Full Load Amps = 90 Amps
5% 5%
1,800 Amps
The breaker or fuse would have a minimum interrupting rating
of 1,800 amps at 480 volts.
NOTE: The secondary voltage is not used in the calculation.
The reason is the primary circuit of the transformer is the only
winding being interrupted.
21. Can Single Phase Transformers be used
for Three Phase applications? Yes. Three phase
transformers are sometimes not readily available whereas
single phase transformers can generally be found in stock.
Three single phase transformers can be used in delta connected
primary and wye or delta connected secondary. They should
never be connected wye primary to wye secondary, since this
will result in unstable secondary voltage. The equivalent three
phase capacity when properly connected of three single phase
transformers is three times the nameplate rating of each single
phase transformer. For example: Three 10 KVA single phase
transformers will accommodate a 30 KVA three phase load.
22.Does ACME provide “Zig-Zag” Grounding
Transformers? Yes. Please refer to Page 31 for a special
diagram which can be used to connect standard single phase
off-the-shelf transformers in a three phase zig-zag manner.
This system can be used for either grounding or developing a
fourth wire from a three phase neutral. An example would be
to change a 480 V — three phase — three wire system to a
480Y/277 V — three phase — four wire system.
23. What color are ACME Dry-Type Transformers?
ASA 61 (NEMA) light gray is used on all enclosed transformers
from .050 to 500 KVA.
24. How do you select a transformer to operate
in an ambient higher than 40° centigrade? When
the ambient exceeds 40°C use the following chart for de-rating
standard transformers.
Instead of ordering custom built transformers to operate in
ambients higher than 40°C, it is more economical to use a
standard transformer of a larger KVA rating.
SECTION1DRY-TYPE DISTRIBUTION TRANSFORMERS
8 ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION • LUMBERTON, NC • 800-334-5214 • www.acmepowerdist.com
Maximum Ambient Maximum Percentage
Temperature of Loading
40°C (104°F) 100%
50°C (122°F) 92%
60°C (140°F) 84%
H1 H2
x2 x1
120 VOLT
OUTPUT
240 VOLT
INPUT
VOLT
METER
360
VOLT
READING
ADDITIVE
POLARITY
high voltage and one low voltage terminal unconnected. When
the transformer is excited, the resultant voltage appearing
across a voltmeter will be the sum of the high and low voltage
windings. This is useful when connecting single phase transformers
in parallel for three phase operations. Polarity is a term
used only with single phase transformers.
30. What is exciting current? Exciting current, when
used in connection with transformers, is the current or amperes
required for excitation. The exciting current on most lighting
and power transformers varies from approximately 10% on
small sizes of about 1 KVA and smaller to approximately .5%
to 4% on larger sizes of 750 KVA. The exciting current is made
up of two components, one of which is a real component and
is in the form of losses or referred to as no load watts; the other
is in the form of reactive power and is referred to as KVAR.
31. Will a transformer change Three Phase to
Single Phase? A transformer will not act as a phase changing
device when attempting to change three phase to single phase.
There is no way that a transformer will take three phase in and
deliver single phase out while at the same time presenting a
balanced load to the three phase supply system. There are,
however, circuits available to change three phase to two phase
or vice versa using standard dual wound transformers. Please
contact the factory for two phase applications.
32.Can air cooled transformers be applied to
motor loads? This is an excellent application for air cooled
transformers. Even though the inrush or starting current is five
to seven times normal running current, the resultant lower
voltage caused by this momentary overloading is actually
beneficial in that a cushioning effect on motor starting is the
result. The tables on Pages 11 and 12 illustrate some typical
transformer requirements for use with motor applications.
33. How is an Acme Drive Isolation Transformer
(DIT) different than a General Purpose
Transformer? DITs, as the name implies, are designed to
be used with motor drives (AC and DC) and to provide isolation
from the service line. They are specifically designed to withstand
the“short circuit like”duty imposed by the firing of the thyristors.
Harmonics generated by drives create added loads on the
transformer. Therefore, it is important that a transformer of
equal or greater KVA to that recommended by the drive
manufacturer be installed for a particular motor application.
34. How are transformers sized to operate
Three Phase induction type squirrel cage
motors? The minimum transformer KVA rating required to
operate a motor is calculated as follows:
Minimum Transformer KVA =
Running Load Amperes x 1.73
x Motor Operating Voltage
1000
NOTE: If motor is to be started more than once per hour add
20% additional KVA.
Care should be exercised in sizing a transformer for an induction
type squirrel cage motor as when it is started, the lock rotor
amperage is approximately 5 to 7 times the running load
amperage. This severe starting overload will result in a drop
of the transformer output voltage. When the voltage is low the
SECTION1DRY-TYPE DISTRIBUTION TRANSFORMERS
ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION • LUMBERTON, NC • 800-334-5214 • www.acmepowerdist.com 9
torque and the horsepower of the motor will drop proportionately
to the square of the voltage. For example: If the voltage
were to drop to 70% of nominal, then motor horsepower and
torque would drop to 70 % squared or 49% of the motor
nameplate rating.
If the motor is used for starting a high torque load, the motor
may stay at approximately 50% of normal running speed as
illustrated by the graph below:
The underlying problem is low voltage at the motor terminals. If
the ampere rating of the motor and transformer overcurrent
device falls within the motor’s 50% RPM draw requirements,
a problem is likely to develop. The overcurrent device may not
open under intermediate motor ampere loading conditions.
Overheating of the motor and/or transformer would occur,
possibly causing failure of either component.
This condition is more pronounced when one transformer is
used to power one motor and the running amperes of the
motor is in the vicinity of the full load ampere rating of the
transformer. The following precautions should be followed:
(1) When one transformer is used to operate one motor, the
running amperes of the motor should not exceed 65% of
the transformer’s full load ampere rating.
(2) If several motors are being operated from one transformer,
avoid having all motors start at the same time. If this is
impractical, then size the transformer so that the total running
current does not exceed 65% of the transformer’s full
load ampere rating.
35. Why are Small Distribution Transformers
not used for Industrial Control Applications?
Industrial control equipment demands a momentary overload
capacity of three to eight times normal capacity. This is most
prevalent in solenoid or magnetic contactor applications where
inrush currents can be three to eight times as high as normal
sealed or holding currents but still maintain normal voltage at
this momentary overloaded condition. Distribution transformers
are designed for good regulation up to 100 percent loading, but
their output voltage will drop rapidly on momentary overloads
of this type making them unsuitable for high inrush applications.
Industrial control transformers are designed especially for
maintaining a high degree of regulation even at eight times
normal load.This results in a larger and generally more expensive
transformer. For a complete listing of ACME industrial control
transformers, refer to Section V.
50 100 150 200 250
20
40
60
80
100
SPEED (PERCENT OF
SYNCHROUS SPEED)
TORQUE (PERCENT OF FULL LOAD TORQUE)
SPEED vs TORQUE FOR A TYPICAL THREE PHASE
INDUCTION TYPE SQUIRREL CAGE MOTOR
STALL
ZONE
36. Can 4-Winding Single Phase Transformer be
auto-connected? Yes. There are occasions where 480 volts
single phase can be stepped down to 240 volts single phase by
autoconnecting a standard 4-winding isolating transformer as
shown in Figure 1. If connected in this manner, the nameplate
KVA is doubled. For example: A 10 KVA load can be applied to
a 5 KVA 4-winding transformer if connected per Figure 1.
37. What about balanced loading on Three
Phases? Each phase of a three phase transformer must be
considered as a single phase transformer when determining
loading. For example: A 45 KVA three phase transformer with a
208Y/120 volt secondary is to service 4 loads at 120 volts single
phase each. These loads are 10 KVA, 5 KVA, 8 KVA,and 4 KVA.
NOTE: that maximum loading on any phase does not exceed
10 KVA. Each phase has a 15 KVA capacity.
45 KVA
3 phase
= 15 KVA per phase
If incorrect method is used, phase B will have an 18 KVA load
which is 3 KVA above its normal capacity of 15 KVA and failure
will result even though we only have a total load of 27 KVA on
a 45 KVA transformer.
SECTION1DRY-TYPE DISTRIBUTION TRANSFORMERS
10 ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION • LUMBERTON, NC • 800-334-5214 • www.acmepowerdist.com
38. What is meant by “Balanced Loading” on
Single Phase Transformer applications? Since
most single phase transformers have a secondary voltage of
120/240, they will be operated as a three wire system. Care
must be taken in properly distributing the load as the transformer
secondary consists of 2 separate 120 volt windings. Each 120
volt winding is rated at one-half the nameplate KVA rating. For
example: A 10 KVA transformer, 120/240 volt secondary is to
service an 8 KVA load at 240 volts and two 1 KVA loads at
120 volts each.
If the incorrect method is used, winding A will be loaded at
6 KVA, and winding B will be loaded at 4 KVA. These do total
10 KVA but, since each winding is only rated at 5 KVA (1/2 of
nameplate rating), we have an overloaded transformer and a
certain failure.
39. What are typical applications for
transformers? ACME transformers should be specified to:
(1) Distribute power at high voltage.
(2) Eliminate double wiring.
(3) Operate 120 volt equipment from power circuits.
(4) Insulate circuits/establish separately derived circuits.
(5) Provide 3-wire secondary circuits.
(6) Buck and Boost (See Section VII).
(7) Provide electrostatic shielding for transient noise protection.
Figure 1
H1
480V
H3 H2 H4 X1 X3 X2 X4
240V
Enclosure Definitions
Type 1 Enclosures— are intended for indoor
use, primarily to provide a degree of protection against
contact with the enclosed equipment.
Type 2 Enclosures— are intended for indoor
use, primarily to provide a degree of protection against
limited amounts of falling water and dirt.
Type 3R Enclosures — are intended for outdoor
use, primarily to provide a degree of protection against
falling rain, sleet and external ice formation.
Definitions Pertaining to Enclosures
Ventilated — means constructed to provide for
circulation of external air through the enclosure to
remove excess heat, fumes or vapors.
Non-Ventilated — means constructed to provide
no intentional circulation of external air through the
enclosure.
Indoor Locations — are those areas protected
from exposure to the weather.
Outdoor Locations — are those areas exposed
to the weather.
Hazardous (Classified) Locations — are
those areas, which may contain hazardous (classified)
materials in sufficient quantity to create an explosion.
See Article 500 of The National Electrical Code.
(NEUTRAL)
10 KVA
8 KVA 5 KVA 4 KVA
A
B
C
CORRECT WAY:
(NEUTRAL)
10 KVA
5 KVA 4 KVA
A
B
C
INCORRECT WAY:
8 KVA
CORRECT WAY:
120V 1 KVA
120V
240V 8 KVA
1 KVA
A
B
INCORRECT WAY:
120V 1 KVA 1 KVA
120V
240V 8 KVA
SECTION ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION • LUMBERTON, NC • 800-334-5214 • www.acmepowerdist.com 11
DRY-TYPE DISTRIBUTION TRANSFORMERS
① When motor service factor is greater than 1,
increase full load amps proportionally.
Example: If service factor is 1.15, increase
above amp values by 15%.
1 Phase KVA = Volts x Amps
1000
NOTE: If motors are started more than once per
hour, increase minimum transformer KVA by 20%.
Steps for Selecting the Proper Transformer
SINGLE PHASE LOADS
1. Determine electrical load
A.Voltage required by load.
B.Amperes or KVA capacity required by load.
C. Frequency in Hz (cycles per second).
D.Verify load is designed to operate on a single phase supply.
All of the above information is standard data normally obtained from equipment
nameplates or instruction manuals.
2. Determine supply voltage
A.Voltage of supply (source).
B. Frequency in Hz (cycles per second).
The frequency of the line supply and electrical load must be the same. Select
single phase transformer designed to operate at this frequency, having a primary
(input) equal to the supply voltage and a secondary (output) equal to the voltage
required by the load.
3. If the load nameplate expresses a rating in KVA, a transformer can be
directly selected from the charts. Choose from a group of transformers with
primary and secondary voltages matching those you have just determined.
A. Select a transformer with a standard KVA capacity equal to or greater than
that needed to operate the load.
B. Primary taps are available on most models to compensate for line voltage
variations. (Refer to question #2 in the Transformer Questions and Answers
Section on page 6.)
C. When load ratings are given only in amperes, tables 1 and 2 or the following
formulas may be used to determine proper KVA size for the required transformer.
(1) To determine KVA when volts and amperes are known:
KVA = Volts x Amps
1000
(2) To determine Amperes when KVA and volts are known:
Amps = KVA x 1000
Volts
Single Phase Example
Question: Select a transformer to meet the following conditions. Load is single
phase lighting using incandescent lamps. Each fixture requires 1.3 amps @ 120
volts, 1 phase, 60 Hz, power factor of unity. The installation requires 52-100 watt
fixtures. The desired circuit distributing power to the light fixtures is 120/240 volt,
three wire, single phase. The supply voltage is 460 volt, 3 phase.
Answer: Compute the KVA required.
1.3 amps x 120 volts = .156 KVA
1000
For each lighting fixture
Always use amps x volts to compute VA, never use lamp wattage. .156 KVA/
Fixture x 52 Fixture = 8.11 KVA. The two sizes (KVA) nearest 8.11 KVA are 7.5 KVA
and 10 KVA. Use the 10 KVA. This will not overload the transformer and allows some
capacity, 1.89 KVA, for future loads. Since the supply is 460 V (not 480 V) use the
456 V tap. This will produce approximately 120 volts on output. If the tap is not used,
the output will be 115 V compared to the desired 120 V. Note the transformer
selected is single phase but the supply is 480 V, 3 phase. Single phase is obtained
by using any 2 wires of the 3 phase supply.
TABLE 1
Full Load Current in Amperes–
Single Phase Circuits
MIN.
HORSE- 115 V 208 V 230 V TRANSPOWER
FORMER
KVA
1/6 4.4 2.4 2.2 .53
1/4 5.8 3.2 2.9 .70
1/3 7.2 4.0 3.6 .87
1/2 9.8 5.4 4.9 1.18
3/4 13.8 7.6 6.9 1.66
1 16 8.8 8 1.92
1.5 20 11.0 10 2.40
2 24 13.2 12 2.88
3 34 18.7 17 4.10
5 56 30.8 28 6.72
7.5 80 44 40 9.6
10 100 55 50 12.0
TABLE 2
Full Load Amperes
Single Phase A.C. Motors ①
KVA 120V 208V 240V 277V 380V 440V 480V 600V
.050 0.4 0.2 0.2 0.2 0.1 0.1 0.1 0.1
.100 0.8 0.5 0.4 0.3 0.2 0.2 0.2 0.2
.150 1.2 0.7 0.6 0.5 0.4 0.3 0.3 0.3
.250 2.0 1.2 1.0 0.9 0.6 0.5 0.5 0.4
.500 4.2 2.4 2.1 1.8 1.3 1.1 1.0 0.8
.750 6.3 3.6 3.1 2.7 2.0 1.7 1.6 1.3
1 8.3 4.8 4.2 3.6 2.6 2.3 2.1 1.7
1.5 12.5 7.2 6.2 5.4 3.9 3.4 3.1 2.5
2 16.7 9.6 8.3 7.2 5.2 4.5 4.2 3.3
3 25 14.4 12.5 10.8 7.9 6.8 6.2 5.0
5 41 24.0 20.8 18.0 13.1 11.3 10.4 8.3
7.5 62 36 31 27 19.7 17 15.6 12.5
10 83 48 41 36 26 22.7 20.8 16.7
15 125 72 62 54 39 34 31 25
25 208 120 104 90 65 57 52 41
37.5 312 180 156 135 98 85 78 62
50 416 240 208 180 131 114 104 83
75 625 360 312 270 197 170 156 125
100 833 480 416 361 263 227 208 166
167 1391 802 695 602 439 379 347 278
250 2083 1201 1041 902 657 568 520 416
1
SECTION1DRY-TYPE DISTRIBUTION TRANSFORMERS
12 ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION • LUMBERTON, NC • 800-334-5214 • www.acmepowerdist.com
THREE PHASE LOADS
1. Determine electrical load
A.Voltage required by load.
B.Amperes or KVA required by load.
C. Frequency in Hz (cycles per second).
D.Verify load is designed to operate on three phase.
All the above information is standard data normally obtained from equipment
nameplates or instruction manuals.
2. Determine supply voltage
A.Voltage of supply (source).
B. Frequency in Hz (cycles per second).
The frequency of the line supply and electrical load must be the same. A three
phase transformer is selected which is designed to operate at this frequency
having a primary (input) equal to the supply voltage and a secondary (output)
equal to the voltage required by the load.
3. If the load nameplate expresses a rating in KVA, a transformer can be
directly selected from the charts. Choose from the group of transformers
with primary and secondary voltages matching that which you have
just determined.
A.Select a transformer with a standard KVA capacity equal to or greater than
that needed to operate the load.
B.Primary taps are available on most models to compensate for line voltage
variations. (Refer to question #2 in the Transformer Questions and Answers
Section on page 6.)
C. When load ratings are given only in amperes, tables 3 and 4 or the following
formulas may be used to determine properKVA size for the required transformer.
(1) To determine three phase KVA when volts and amperes are known:
Three Phase KVA =
Volts x Amps x 1.73
1000
(2) To determine Amperes when KVA and volts are known:
Amps =
3 Phase KVA x 1000
Volts x 1.73
Three Phase Example
Question: Select a transformer to fulfill the following conditions. Load is a three phase
induction motor, 25 horsepower @ 240 volts, 60 Hz and a heater load of 4 kilowatts
@ 240 volts single phase. The supply voltage is 480Y/277, three phase, 4 wire.
Answer: Compute the KVA required. Motor—From table 4 the current is 68 amps.
240 volts x 68 amps x 1.73 = 28.2 KVA
1000
(The KVA can also be obtained from table 4).
Heater — 4 KVA
A three phase transformer must be selected so that any one phase is not overloaded.
Each phase should have the additional 4 KVA rating required by the heater even though
the heater will operate on one phase only. So, the transformer should have a minimum
KVA rating of 28.2 + 4 + 4 + 4 or 40.2 KVA. Refer to the appropriate selection chart.
A 480 delta primary—240 delta secondary transformer may be used on a 4 wire,
480Y/277 volt supply. The fourth wire (neutral) is not connected to the transformer.
To not overload the transformer, a 45 KVA transformer should be selected.
NOTE: Any two wires of the 240 volts, 3 phase developed by the secondary of the
transformer may be used to supply the heater. Any 2 wires of a 3 phase system
is single phase.
TABLE 3
Full Load Current in Amperes–
Three Phase Circuits
TABLE 4
Full Load Amperes
Three Phase A.C. Motors ①
① When motor service factor is greater than 1,
increase full load amps proportionally.
Example: If service factor is 1.15, increase
above amp values by 15%.
3 Phase KVA = Volts x Amps x 1.73
1000
NOTE: If motors are started more than once per
hour, increase minimum transformer KVA by 20%.
MIN.
HORSE- 208 V 230 V 460 V 575 V TRANSPOWER
FORMER
KVA
1/2 2.2 2.0 1.0 0.8 0.9
3/4 3.1 2.8 1.4 1.1 1.2
1 4.0 3.6 1.8 1.4 1.5
2 7.5 6.8 3.4 2.7 2.7
3 10.7 9.6 4.8 3.9 3.8
5 16.7 15.2 7.6 6.1 6.3
10 31 28 14 11 11.2
15 46 42 21 17 16.6
20 59 54 27 22 21.6
25 75 68 34 27 26.6
30 88 80 40 32 32.4
40 114 104 52 41 43.2
50 143 130 65 52 52
60 170 154 77 62 64
75 211 192 96 77 80
100 273 248 124 99 103
125 342 312 156 125 130
150 396 360 180 144 150
200 528 480 240 192 200
KVA 208 V 240 V 380 V 440 V 480 V 600 V
3 8.3 7.2 4.6 3.9 3.6 2.9
4.5 12.5 10.8 6.8 5.9 5.4 4.3
6 16.6 14.4 9.1 7.8 7.2 5.8
9 25 21.6 13.7 11.8 10.8 8.6
15 41 36 22.8 19.6 18.0 14.4
22.5 62 54 34.2 29 27 21.6
30 83 72 45.6 39 36 28
45 124 108 68.4 59 54 43
75 208 180 114 98 90 72
112.5 312 270 171 147 135 108
150 416 360 228 196 180 144
225 624 541 342 294 270 216
300 832 721 456 392 360 288
500 1387 1202 760 655 601 481
750 2081 1804 1139 984 902 721
1000 2775 2405 1519 1312 1202 962
SECTION1DRY-TYPE DISTRIBUTION TRANSFORMERS
ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION • LUMBERTON, NC • 800-334-5214 • www.acmepowerdist.com 13
UL-3R Enclosures
SINGLE PHASE, .05 to .150 KVA
■ Installation keyhole mounting slots for mounting
bolts prior to installation. Mounting slots are
accessible from the front. Lifting ears are included
on 3 to 25 KVA units.
■ Wiring flexible copper leadwire terminations for
easy connections outside the front access wiring
compartment. Dual size knockouts in both sides
and the bottom of the wiring compartment for
greater wiring convenience and flexibility.
FEATURES
■ UL listed, CSA certified and UL-3R enclosure meets or exceeds all listing
criteria including NEMA, ANSI and OSHA standards.
■ Easy and convenient installation to meet your requirements, the transformer
can be mounted in any position.
■ Long Life UL class 130°C insulation system. Transformers can be banked for
three phase service.
■ Large wiring compartment, no conduit or pull boxes required. Front access
for wiring ease. Wiring compartment remains cool.
■ Completely enclosed UL-3R enclosure for indoor/outdoor service. Rugged
non-ventilated construction.
■ Plenty of knockouts for multi-directional entry.
■ All copper lead wire terminations.
■ Ground studs for use with non-metallic conduit.
FEATURES
■ UL listed, CSA certified and UL-3R enclosures meets or exceeds
all listing criteria including NEMA, ANSI and OSHA standards.
■ Shielded for cleaner power.
■ Encapsulated and completely enclosed design electrical grade
silica and resin compounds completely enclose the core and
coil to seal out all moisture and air. UL Type 3R enclosure for
indoor or outdoor service. Encapsulation eliminates corrosion and
insulation deterioration.
■ Quiet operation with sound levels well below NEMA standards.
■ Long life UL class 155°C insulation system. 115°C rise thru
.750 KVA; 180°C insulation system, 115°C rise, 1 KVA and above.
SINGLE PHASE, .250 to 25 KVA
316 STAINLESS STEEL
TRANSFORMERS
FEATURES
■ 3R enclosure.
■ Comply with NEC Class 1, Division 2, when installed
per NEC 501-2 (b).
■ Encapsulated construction.
■ Single phase: 0.25 – 25 KVA.
Three phase: 3 – 7.5 KVA.
■ Core and Coil assembly completely encapsulated in
polyester or epoxy seals out all moisture, eliminating
corrosion and deterioration of insulation.
■ Electrostatic shielding.
APPLICATIONS
■ Harsh industrial locations
■ Corrosive chemical exposure
■ Waste water treatment facilities
■ Coastal or marine applications with high salt mist
■ Any application where painted cold roll steel is not adequate
SECTION1DRY-TYPE DISTRIBUTION TRANSFORMERS
14 ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION • LUMBERTON, NC • 800-334-5214 • www.acmepowerdist.com
Shielded Power in Many Design Styles
THREE PHASE 3 to75 KVA
FEATURES
■ UL listed, CSA certified and UL-3R enclosure meets or
exceeds all listing criteria including NEMA, ANSI and
OSHA standards.
■ UL Class 180°C insulation system. 115°C rise.
■ Extra large front access wiring compartment through 9 KVA;
top access through 75 KVA for easier installation and cooler
case temperatures.
■ Completely enclosed — suitable for indoor/outdoor service.
Consult selection charts for details. Excellent for dust or lint
laden atmosphere.
■ Encapsulated — electrical grade silica and resin compound
completely encloses the core and coil. Encapsulation
seals out all moisture and air, eliminating corrosion and
insulation deterioration.
■ High efficiency and excellent regulation.
■ Sound levels below NEMA standards.
■ Keyhole mounting slots permit installation of mounting
bolts prior to hanging transformer and are accessible from
the front. Lifting ears for easy installation.
■ Wiring connections can be made outside of wiring
compartment due to the use of flexible leads.
■ 3-9 KVA provided with dual size knockouts in sides and
bottom of wiring compartment.
■ Termination — copper lead wire.
■ Electrostatic shielding provided on all 60 Hz isolation
transformers.
NOTE: Units above 15 KVA apply to Groups F and K.
NEW
15
SECTION1DRY-TYPE DISTRIBUTION TRANSFORMERS
ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION • LUMBERTON, NC • 800-334-5214 • www.acmepowerdist.com
FEATURES
■ With weather shield, UL Type 3R enclosure type 2 enclosure
without weather shield. UL listed and CSA certified.
■ UL Class 220°C insulation system, 150°C rise.
■ Extra large wiring compartment for easier installation and
cooler case temperatures.
■ NEMA standard bus bar terminals, no special tools needed
to make clearly marked connections. Tap changing easily
accomplished with jumpers.
■ Aluminum windings for increased insulation life, cooler
operation, lower losses.
■ Noise and vibration isolating pads standard to assure
quiet operation.
■ Large permanently legible nameplates on front.
■ Single phase units can be banked for 3 phase service.
■ All units have ground studs for use with non-metallic conduit.
■ Suitable for wall or “trapeze” mounting. Wall brackets are
available for units up to 50 KVA single and 75 KVA three phase.
■ Other models are available with class 220°C insulation and
either 115°C or 80°C rise operating temperature. Refer to
Opti-Miser® Section.
■ Termination — single phase 37.5 to 100 KVA, copper bus;
167 to 250 KVA, aluminum bus. Three phase 27 to 225 KVA,
copper bus; 275 to 1000 KVA, aluminum bus.
■ Electrostatic shielding provided on all 60 Hz isolation
transformers.
■ Electrostatic shielding not available on Groups D1and G1.
SINGLE PHASE 37.5 to 250 KVA
THREE PHASE 25 to 1000 KVA
LN SERIES
LOW NOISE TRANSFORMERS
FEATURES
■ 3 db below NEMA standard (LN3).
■ Contact factory for 5 db below.
■ Encapsulated construction.
■ Three phase: 30 – 225 KVA, 480 Delta to 208Y/120.
30 – 225 KVA, 480 Delta to 208Y/120.
■ NEMA TP1 option available (contact factory).
■ Aluminum windings standard.
■ Copper windings available (contact factory).
■ NEMA 2 enclosures (3R with weather shield).
■ 220°C Insulation with 150°C Rise.
■ Electrostatic shielding.
APPLICATIONS
■ Theaters
■ Hospitals
■ Educational facilities
■ Office buildings
■ Any application where transformers need to be installed in
or near occupied areas
■ Churches
■ Libraries
NEW
16
SECTION1DRY-TYPE DISTRIBUTION TRANSFORMERS
ACME ELECTRIC, POWER DISTRIBUTION PRODUCTS DIVISION • LUMBERTON, NC • 800-334-5214 • www.acmepowerdist.com
Aluminum
strip coils
Vibration
isolation pads
Design allows easy
cable/conduit entry
Metal brace for
added strength
Copper
secondary bus
Punched bottom
for ventilation
Ground
Copper stud bolt
primary bus
Fiberglass
terminal board
Copper tap
connections
Wound core
NOTE: These photographs are for illustration purposes only. Please contact factory for construction details.
Lifting ears
Sand and resin
encapsulation
Primary copper
leadwires
Front access opening
Secondary copper
leadwires
Electrostatic shield
ground point & ground stud
Wound Core construction for
lower losses and quiet operation.
Resin Encapsulation seals out moisture,
dirt and eliminates corrosion. Excellent
choice for use in harsh environments.
Large wiring
compartment
Photo representative of Drive Isolation Transformer