Table A
The table below helps you to select the gauge and turns per sq. cm of copper wire by matching them with the selected current rating of the winding appropriately.
SWG------- (AMP)------- Turns per Sq.cm.
10----------- 16.6---------- 8.7
11----------- 13.638------- 10.4
12----------- 10.961------- 12.8
13----------- 8.579--------- 16.1
14----------- 6.487--------- 21.5
15----------- 5.254--------- 26.8
16----------- 4.151--------- 35.2
17----------- 3.178--------- 45.4
18----------- 2.335--------- 60.8
19----------- 1.622--------- 87.4
20----------- 1.313--------- 106
21----------- 1.0377-------- 137
22----------- 0.7945-------- 176
23----------- 0.5838--------- 42
24----------- 0.4906--------- 286
25----------- 0.4054--------- 341
26----------- 0.3284--------- 415
27----------- 0.2726--------- 504
28----------- 0.2219--------- 609
29----------- 0.1874--------- 711
30----------- 0.1558--------- 881
31----------- 0.1364--------- 997
32----------- 0.1182--------- 1137
33----------- 0.1013--------- 1308
34----------- 0.0858--------- 1608
35----------- 0.0715--------- 1902
36----------- 0.0586---------- 2286
37----------- 0.0469---------- 2800
38----------- 0.0365---------- 3507
39----------- 0.0274---------- 4838
40----------- 0.0233---------- 5595
41----------- 0.0197---------- 6543
42----------- 0.0162---------- 7755
43----------- 0.0131---------- 9337
44----------- 0.0104--------- 11457
45----------- 0.0079--------- 14392
46----------- 0.0059--------- 20223
47----------- 0.0041--------- 27546
48----------- 0.0026--------- 39706
49----------- 0.0015--------- 62134
50----------- 0.0010--------- 81242