Code of practice for power system protection


01 The entire wiring of circuitry for indications, alarms, metering and protection should be permanent wiring.
02 The leads should be marked and identified by ferrules near terminals.
03 Every lead should end at a terminal point and no junction by twisting is allowed.
04 The wiring should be by copper leads for C.T secondary for all cores i.e. metering cores as well as protection cores and for PT secondary for protection core.
05 The wiring should be by copper leads 1.07 The copper lead for 1.05 & 1.06 above should be stranded but not single lead type.
06 Aluminum leads can be used for indication, alarms and PT secondary for metering but stranded wires only are to be used. But copper leads are always preferable for these said purposes.
07 The terminations should be lugged by ring shape ‘O’ lugs. ‘U’ shape lugs should be avoided since ‘U’ shape lugs may slip if terminal is loosen.
08 For CT Secondary terminations, two nuts with one spring washer and two flat washers to be compulsorily used.
09 The CT terminal strips should be stud type with nuts and not screw-in-type.
10 Wherever two sets of batteries are available, the primary protection and back-up protection should be from different batteries.
11 Where there is only one battery at an Electrical Power Substation, the primary and back-up protections should be given D.C supply through two individual circuits with independent fuses run from D.C bus.
12 When CBs have two trip coils, both main protection and backup protection will energize both the trip coils.
13 D.C and A.C supplies should not be taken through different cores of the same cable. Totally different cables should be used for DC and AC supplies.
14 Independent D.C cables should be run to each equipment in the yard and looping of D.C supply from one equipment to other is not permitted.
15 The D.C emergency lighting in substation should be through independent cables and not mixed up with protection and other circuitry.
16 Standard color codes for wires in control circuit of different sizes should be as follows,
PURPOSESIZECOLOR
Indication, Alarm, trip, close etc1.5 mm2Gray
Red Phase Metering PT Circuit1.5 mm2Red
Yellow Phase Metering PT Circuit1.5 mm2Yellow
Blue Phase Metering PT Circuit1.5 mm2Blue
Red Phase Protection PT Circuit2.5 mm2Red
Yellow Phase Protection PT Circuit2.5 mm2Yellow
Blue Phase Protection PT Circuit2.5 mm2Blue
Red Phase Metering and Protection CT Circuit2.5 mm2Red
Yellow Phase Metering and Protection CT Circuit2.5 mm2Yellow
Blue Phase Metering and Protection CT Circuit2.5 mm2Blue
Phase for auxiliary AC supply2.5 mm2Red
Neutral for auxiliary AC supply2.5 mm2Black
Common star point of CTs2.5 mm2Black
Common star point of Protection PTs2.5 mm2Black
Common star point of Metering PTs1.5 mm2Black
Earthing Connection2.5 mm2Green
17 The lead numbers are also standardized as follows so that anyone can easily identify the purpose for which the lead is connected
Alphabet SeriesPurposeExample
J SeriesD.C IncomingJ1, J2, etc.
K SeriesControl – Closing, Tripping, etc.K1, K2, K3 etc.
L SeriesAlarms, indications and annunciationsL1, L2, L3, etc.
M SeriesMotor CircuitM1, M2, etc.
E SeriesPotential transformer secondariesE1, E2, E3, etc.
H SeriesLT A.C SupplyH1, H2, H3, etc..
A SeriesC.T secondary for special protectionA1, A2, A3, etc.
B SeriesBus bar protectionB1, B2, B3, etc..
C SeriesProtection CircuitsC1, C2, C3, etc.
D SeriesMetering CircuitD1, D2, D3, etc.
18 The CT ratios available and adopted with number of cores shall be displayed on each panel as follows: (with underlined position as adopted).
400 – 200 – 100 / 1-1-1
19 Wherever CT cores are not used “SHORTING LOOPS” should be provided in CT secondary terminals and not in marshaling boxes or at panels.
20 The Cable entries in the equipment, marshaling boxes and panels should be through appropriate size of cable glands. No other means are allowed.
21 PT secondaries should have group MOCBs with D.C alarm.
22 Few cells from a battery set should not be used for separate low voltage D.C circuits. Here D.C – D.C converters may be employed for utilizing full D.C voltage of the entire battery as input.

Standard lead numbers used in control circuit of protection of power system

Certain lead numbers are standardized as follows and should be compulsorily adopted with ferrules at terminations of leads.
Main DC Positive supply – J1

Main DC Negative supply – J2

DC Positive bus inside panel – K1

DC Nagetive bus inside panel – K2
Remote Close - K15R

Remote Trip - K5R

Local Close - K15L

Local Trip - K5L

Metering CT secondaries – D11, D31, D51, D71 etc.

Protection CT secondaries – C11, C31, C51, C71 etc.

Special Protection CT secondaries – A11, A31, A51, A71 etc.

PT scondaries – E11, E31, E51, E71 etc.

Different relay device number used in protection of power system

Mark NumberName of the Device
2Time delay relay
3Checking or Interlocking relay
21Distance relay
25Check synchronizing relay
27Under voltage relay
30Annunciator relay
32Directional power (Reverse power) relay
37Low forward power relay
40Field failure (loss of excitation) relay
46Negative phase sequence relay
49Machine or Transformer Thermal relay
50Instantaneous Over current relay
51A.C IDMT Over current relay
52Circuit breaker
52aCircuit breaker Auxiliary switch “Normally open” (‘a’ contact)
52bCircuit breaker Auxiliary switch “Normally closed” (‘b’ contact)
55Power Factor relay
56Field Application relay
59Overvoltage relay
60Voltage or current balance relay
64Earth fault relay
67Directional relay
68Locking relay
74Alarm relay
76D.C Over current relay
78Phase angle measuring or out of step relay
79AC Auto reclose relay
80Monitoring loss of DC supply
81Frequency relay
81UUnder frequency relay
81OOver frequency relay
83Automatic selective control or transfer relay
85Carrier or pilot wire receive relay
86Tripping Relay
87Differential relay
87GGenerator differential relay
87GTOverall differential relay
87UUAT differential relay
87NTRestricted earth fault relay
95Trip circuit supervision relay
99Over flux relay
186AAuto reclose lockout relay
186BAuto reclose lockout relay

Post a Comment

0 Comments

Close Menu